Thermo Products Heat Pump THJF18 THRU 60 User Manual

TABULAR DATA SHEET  
Outdoor Split System Heat Pump 1.5 Thru 5 Tons  
MODELS: THJF18* THRU 60  
14.5 SEER – R-410A, 1 PHASE  
Physical and Electrical Data  
THJF18  
S41S3  
THJF24  
S41S3  
THJF30  
S41S3  
THJF36  
S41S3  
THJF42  
S41S3  
THJF48  
S41S3  
THJF60  
S41S3  
MODEL  
Unit Supply Voltage  
208-230V, 1 60Hz  
Normal Voltage Range 1  
Minimum Circuit Ampacity  
Max. Overcurrent Device Amps 2  
187 to 252  
23.7  
11.9  
20  
17.6  
30  
17.3  
30  
26.1  
45  
28.8  
50  
35.3  
60  
40  
Min. Overcurrent Device Amps 3  
Compressor Type  
15  
Scroll  
9.0  
20  
Scroll  
13.4  
58.3  
No  
20  
Scroll  
12.8  
64.0  
No  
25  
Scroll  
17.9  
96.7  
No  
30  
Scroll  
19.8  
115.0  
No  
30  
Scroll  
28.8  
115.0  
No  
40  
2-Stage Scroll  
35.3  
118.0  
No  
Rated Load  
Compressor  
Amps  
Locked Rotor  
48.0  
No  
Crankcase Heater  
Factory External Discharge Muffler  
Factory External Check Valve  
Yes  
No  
Yes  
No  
Yes  
No  
Yes  
No  
Yes  
No  
Yes  
No  
Yes  
No  
HS Kit Required with TXV 4  
No  
No  
No  
No  
No  
No  
No  
Fan Motor Amps  
Rated Load  
0.7  
0.8  
1.3  
1.3  
1.3  
1.3  
1.3  
Fan Diameter Inches  
24  
22  
24  
24  
24  
24  
24  
Rated HP  
1/10  
825  
2000  
15.72  
1
1/8  
1/4  
1/4  
1/4  
1/4  
1/4  
Fan Motor  
Coil  
Nominal RPM  
Nominal CFM  
Face Area Sq. Ft.  
Rows Deep  
1075  
2000  
19.17  
1
850  
3900  
23.58  
1
850  
3900  
23.58  
1
850  
3900  
23.58  
1
850  
3800  
23.58  
2
850  
3800  
23.58  
2
Fin / Inches  
22  
22  
22  
22  
22  
18  
18  
Liquid Line Set OD (Field Installed)  
Vapor Line Set OD (Field Installed)  
Unit Charge (Lbs. - Oz.) 5  
Charge Per Foot, Oz.  
Operating Weight Lbs.  
3/8  
3/8  
3/8  
3/8  
3/8  
3/8  
3/8  
3/4  
3/4  
3/4  
3/4  
7/8  
7/8  
1-1/8  
14 - 2  
0.75  
290  
6 - 15  
0.62  
145  
7 - 14  
0.62  
145  
9 - 14  
0.62  
176  
10 - 9  
0.62  
193  
10 - 14  
0.67  
198  
14 - 2  
0.67  
248  
1. Rated in accordance with ANSI/AHRI Standard 110-2002, utilization range “A”.  
2. Dual element fuses or HACR circuit breaker. Maximum allowable overcurrent protection.  
3. Dual element fuses or HACR circuit breaker. Minimum recommended overcurrent protection.  
4. See Hard Start Kit Accessory Installation Manual for Hard Start Kit part number for each model.  
5. The Unit Charge is correct for the outdoor unit, matched indoor coil, and 15 feet of refrigerant tubing. For tubing lengths other than 15 feet,  
add or subtract the amount of refrigerant, using the difference in length multiplied by the per foot value.  
All dimensions are in inches. They are subject to change without notice.  
Certified dimensions will be provided upon request.  
C
Dimensions  
(Inches)  
Refrigerant Connection  
Service Valve Size  
Unit  
Model  
A1  
28  
40  
40  
40  
40  
40  
40  
B
C
Liquid  
Vapor  
34  
29  
34  
34  
34  
34  
34  
34  
29  
34  
34  
34  
34  
34  
18  
24  
30  
36  
42  
48  
60  
A
3/4”  
3/8”  
7/8”  
B
1. Including Fan Guard.  
MAC-222  
ECN 5287-MA 121005  
 

Technics Stereo System SC S2350 User Manual
Telex Speaker DL18MT User Manual
Thermaltake Ventilation Hood Armor+ User Manual
Timex Watch 568 095003 User Manual
TRENDnet Switch TEG 2248WS User Manual
Troy Bilt Chipper 8 HP User Manual
Uniden Baby Monitor UBR243 User Manual
Vivitek Projector D5010 User Manual
VTech Telephone 5873 User Manual
Walker Indoor Furnishings W52C2DWBL User Manual