Toshiba Network Card BCN002Z User Manual

E6581402c  
TOSVERT VF-FS1 series  
®
BACnet option unit  
Instruction Manual  
NOTICE  
1. Make sure that this instruction manual is delivered to the end user of BACnet® option  
unit.  
2. Read this manual before installing or operating the BACnet® option unit. Keep it in a  
safe place for reference.  
3. All information contained in this manual are subject to change without notice. Please  
confirm the latest information on our web site ³www.inverter.co.jp´.  
 
E6581402c  
Limitation of use  
Safety precaution  
Never use this unit with any device other than TOSVERT VF-FS1 series inverters. Doing so may cause  
an accident.  
Handling in general  
Danger  
Never disassemble, modify or repair the product.  
Disassembling the product may cause electric shocks, fire or injuries.  
For repairs, call your sales/repair agency.  
Disassemble  
Never  
Do not open the front cover on the inverter while the inverter power is on.  
It may lead to electric shocks.  
Do not remove this option from VF-FS1 while the power is on.  
It may lead to electric shocks.  
Do not put or insert foreign objects such as waste cable, bars or wires into the product.  
Prohibited  
It may lead to electric shocks or fire.  
Do not splash water over the product, and do not wipe the body with a wet cloth.  
It may lead to electric shocks or fire.  
Turn off the power immediately in case of any abnormalities such as smoke, smell or  
abnormal noise.  
Neglect of these conditions may lead to fire.  
For repairs, call your sales/repair agency.  
Mandatory  
Mandatory  
Do not touch the sharp portions (such as leads of parts on the board, the corner of board,  
or etc.) on this option.  
It may lead to injuries.  
Warning  
This option is an electrostatic discharge sensitive device. Handle it, where the  
environment is protected against electrostatic electricity.  
Otherwise, permanent damage to device will result.  
Transportation and installation  
Danger  
Do not apply a dropping shock or other physical shocks.  
Otherwise, damage or malfunction will result.  
Do not install or operate the inverter if it is damaged or any part of it is missing.  
Operating a defective inverter may lead to electric shocks or fire.  
For repairs, call your sales/repair agency.  
Prohibited  
Do not put any flammable material near the product.  
It may catch fire due to the product sparking in the case of a malfunction.  
Use this product under the environmental conditions prescribed in the instruction manual.  
Usage it under any other conditions may result in malfunction.  
An emergency stop device must be installed that fits with system specifications  
(e.g. shut off input power then engage mechanical brake).  
Operation cannot be stopped immediately by the inverter or this unit alone, thus risking an  
accident or injuries.  
Install this option into VF-FS1 and secure it by tightening the terminal board fixing  
screws to the specified torque. Otherwise, it may cause the product falling, the damage,  
or malfunctions.  
Mandatory  
When installing this option, do not touch its sharp portions such as leads of parts on the  
board, the corner of board or etc.  
It may lead to injuries.  
- 2 -  
 
E6581402c  
Wiring  
Warning  
Electrical construction work must be done by a qualified expert.  
Connection of input power by someone who does not have expert knowledge may result  
in electric shocks or fire.  
Turn off input power before wiring.  
Wait at least 10 minutes and make sure that the charge lamp (on the inverter unit) is no  
longer lit. Otherwise, it may lead to electric shocks.  
Tighten the screws on the terminal blocks to the specified torque when connecting cables  
to terminal blocks.  
Mandatory  
Otherwise, it may lead to fire.  
Operations  
Danger  
Do not pull on the cable and connector.  
It may cause damage or malfunctions.  
Prohibited  
Mandatory  
Use this option under the environment specified in the instruction manual.  
Usage under the environment other than them may cause damages or malfunctions or  
an accident.  
Use an additional safety device with your inverter or system to prevent a serious  
accident due to the unit malfunctions.  
Usage without an additional safety device may cause an accident.  
Warning  
Set up ³Communication error trip function (see below)´ to stop the inverter when the  
option unit is deactivated by an unusual event such as an operating error, power outage,  
failure, etc.  
- Communication error trip time (Between the inverter and option board) (f803)  
- Network timeout (f892)  
®
(See the VF-FS1 BACnet Communication Function Manual for details)  
Mandatory  
Disposal  
Deactivated option unit may cause an accident, if the ³Communication error trip  
function´ is not properly set up.  
Make sure that the operation signals are STOP before resetting inverters fault. The  
motor may suddenly start and that may result in injuries.  
Warning  
If you dispose off this unit, have it done by a specialist in industrial waste disposal*.  
Improper disposal may result in explosion of capacitors or produce noxious gases,  
resulting in injuries.  
(*) Persons who specialize in the processing of waste and known as ³Industrial Waste  
Product Collectors and Transporters´ or ³Industrial Waste Disposal Persons.´ If the  
collection, transport and disposal of industrial waste is done by someone who is not  
licensed for that job, it is a punishable violation of the law (Laws in regard to cleaning and  
processing of waste materials).  
Mandatory  
Notes on operation  
Notes  
Avoidinstalling in a place where ambient temperature or/and humidity change sharply.  
Keep the transmission cable separate from the power cable of the inverter to prevent the  
inverter from malfunctioning due to electromagnetic noise.  
Ground of SCR terminal on this option at the grounding terminal separated from those of  
inverters and motors. It may cause malfunction due to noise.  
- 3 -  
 
E6581402c  
Preface  
®
Thank you for purchasing the ³BACnet option (BCN002Z)´ for TOSVERT VF-FS1 inverter. By  
Installing this board into the VF-FS1, data communication can be made with a host computer or  
other device via BACnet network.  
Before using this unit, carefully read this instruction manual in order to completely and correctly  
®
utilize excellent performance of this unit. Besides this instruction manual, the ³VF-FS1 BACnet  
®
Communication Function Manual´ which includes the contents to install into BACnet network is  
prepared. If it is required, please contact with our branch offices, sales offices or web site  
(³VF-FS1 BACnet® Communication Function Manual´: E6581404)  
After reading this instruction manual, please keep it handy for future reference.  
*
BACnet is a registered trademark of ASHRAE.  
- Part numbering  
BCN  
002  
Z
0
±
Revision number  
Cable length ( ³Z´ means ³without cable´ )  
Model number of BACnet option  
Symbol of BACnet option  
- Accessory check list  
BACnet communication option is shipped together with the following accessories. On opening the  
packing case, check to see if the following accessories are contained or not.  
(1) BACnet option board (BCN002Z)  
Board (BCN002Z) ............................................1 pcs  
Connector: MSTB2.5/4-ST-5.08  
Manufactured by PHOENIX CONTACT  
(2) Instruction manual  
English (E6581402).......................................1 copy (This book)  
Instruction  
Manual  
(3) Cabling label & Name plate ............................1 sheet  
(1 cabling label and 2 name plates)  
(4) Insulating sheet ...............................................1 sheet  
- 4 -  
 
E6581402c  
Table of Contents  
1. Overview 㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯 6  
2. Names and functions㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯 6  
2.1. Outline㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯 6  
2.2. Use of RS485 communication port㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯 6  
2.3. LED indicator 㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯 7  
3. Installation and Setup 㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯 8  
3.1. Installation method 㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯 8  
3.2. Description of terminals 㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯 9  
3.3. Network cable connection 㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯 10  
3.4. Network configuration㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯 10  
3.5. Wiring of a control terminal 㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯 11  
4. Parameters 㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯 12  
4.1. Communication parameters 㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯 12  
5. Specifications 㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯 13  
6. Warranty 㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯 14  
- 5 -  
 
E6581402c  
1. Overview  
The BACnet (BCN002Z) interface allows the VF-FS1 inverter to be connected into a BACnet network.  
BACnet MS/TP supports a maximum of 32 nodes for one segment.  
2. Names and functions  
The drawing below shows names and functions of main parts.  
2.1. Outline  
Connector  
Input terminal  
SINK/SOURCE  
VIB/PTC select SW  
Terminal board fixing  
screw hole  
(M3 screw)  
Termination  
resistor SW  
Communication  
condition monitor LED  
B
A
GND SCR  
Optional RS485 communication port  
RS485 communication option can be  
used. However it makes BACnet  
Communication be disabled.  
Detachable terminal  
Network  
communication  
2.2. Use of RS485 communication port  
Serial communication (2-wire RS485) option can be used. However, while it is connected, the  
internal communication line is switched to RS485 then the communication via BACnet network is  
disabled. In this case, communication error trip time (f803) is also active. Use RS485 serial  
communication option specified by Toshiba.  
- 6 -  
 
E6581402c  
2.3. LED indicator  
The option has two LEDs. Those functions are below table.  
COM  
Green  
OFF  
OFF  
ON  
ERR  
Red  
OFF  
2s  
1s  
A
2s  
1s  
1s  
1s  
B
C
D
E
F
State  
A
Comment  
LEDs  
Green LED : OFF  
BACnet board failure  
Red LED : Flashing 5 times in 1 second  
Green LED : OFF  
Red LED  
:
Communication loss detected. Confirm the  
network condition and connection of the cable.  
B
C
D
Flashing 3 times in 2 seconds, Off for 1  
second  
Green LED : ON  
Red LED : OFF 0.5s, ON 0.5s  
Green LED :  
Invalid configuration detected (ADR > max  
master), or an option is connected to RJ45.  
Flashing 3 times in 2 seconds, Off for 1  
second  
Waiting for Auto baud rate detection  
Red LED : OFF  
Green LED : Flashing Intermittent Green  
Red LED : ---  
Green LED : ---  
E
F
Valid message received for this node  
Invalid message received (any node)  
Red LED : Flashing Intermittent Red  
- 7 -  
 
E6581402c  
3. Installation and Setup  
3.1. Installation method  
Install the BACnet communication option to VF-FS1 as follows.  
(1) Turn off the input power of VF-FS1 and wait for at least 10 minutes and then check that the  
CHARGE lamp on VF-FS1 is no longer lit.  
(2) Open the VF-FS1 front cover, remove the terminal board fixing screw and take off the VF-FS1  
standard terminal board.  
(Be careful not to lose the terminal board fixing screw when removed since it may be used again.)  
(3) Perform wiring an inverter before installing BACnet communication option.  
(4) Please attach the insulating sheet in VF-FS1.  
(Fix to the terminal board fixing screw hole and PWB catch pin.)  
(5) Install the BACnet communication option over the insulating sheet and secure it with the board  
fixing screw (tightening torque of M3 tapping screw: 0.7 to 0.8Nm).  
(6) Set up the SW of the board with the input terminal for sink or source.  
(7) Stick the cabling label for BACnet communication option on the standard cabling label stuck on  
the reverse side of the VF-FS1 front cover. And stick the BACnet communication option  
nameplate near the standard nameplate. (Be careful not to cover slits on the VF-FS1 enclosure.  
N.B.: To install or remove the terminal board, make it slide in or out in parallel with board.  
VF-FS1 unit  
Board catching pin  
Cabling label position  
Terminal board fixing screw  
(M3 screw tightening torque: 0.7 to 0.8Nm)  
Board fixing screw hole  
Stick the BCN002Z nameplate  
like bellow figure.  
BCN002Z  
Example  
VF-FS1 name plate  
Insulating seat  
(attached)  
BACnet communication option  
(BCN002Z)  
VF-FS1 Standard terminal board  
- 8 -  
 
E6581402c  
3.2. Description of terminals  
<Control terminals specification>  
Terminal  
Function  
symbol  
Electrical specifications  
Internal circuits  
B
A
GND  
Communication signal (+)  
Communication signal (-)  
Signal common  
47k  
4.7k  
B
A
BACnet communication  
4.7k  
47k  
signal  
EIA-485  
Shield terminal.  
Connect to network ground.  
SCR  
TERM  
GND  
SCR  
120  
SW4  
P24  
SINK SOURCE  
Multifunctional programmable  
contact input.  
F
P24  
No voltage contact input  
24VDC, 5mA or less  
PTC  
SINK/SOURCE can be  
selected with SW.  
820  
4.7k  
N.B. Use contact parts for low  
current.  
F, R  
CC  
R
0 to 10VDC input  
15k  
15k  
3.3k  
Multifunction programmable  
analog input.  
with internal pull-up resistor  
for PTC  
Using this terminal as PTC  
input, set SW2 to PTC side  
and set the parameters  
(f645 and f646) to  
proper value.  
P10  
VIB  
VIB  
VIB  
PTC  
Control circuits equipotential  
terminal  
CC  
P24  
PTC  
P24  
P24  
24 VDC power supply output  
24VDC-50mA  
FLA  
FLB  
1c contact  
30VDC-0.5A  
250VAC-1A (cosIꢀ=1㧕  
250VAC-0.5A (cosIꢀ=0.4)  
FLA  
FLB  
FLC  
Multifunctional programmable  
relay contact outputs  
Ry  
FLC  
Danger  
Do not change switches settings while the power is on.  
It may lead to electric shocks or damage.  
Prohibited  
Mandatory  
Turn off the motor operation signals before setting the parameter and the switch  
(SW), when changing the VIB function. Otherwise, the motor may suddenly start  
and that may result in injuries.  
- 9 -  
 
E6581402c  
3.3. Network cable connection  
Connect the BACnet network cable to communication option as follows.  
Title  
Wire type  
Description  
Shielded twisted cable  
Characteristic impedance  
Distributed impedance between  
conductors  
Between 100 and 130 ohm  
Less than 100pF per meter  
Distributed impedance between Less than 200pF per meter  
conductors and shield  
Foil or braided shields are acceptable.  
1200 meters with AWG18 (0.8mm2)  
Length of an MSTP segment  
Cable sheath should be peeled off by about 7mm.  
For wiring work, use a flat blade screwdriver with a 0.6mm thick and  
3.5mm width blade.  
mm  
Tightening torque for the terminal block is 0.5Nm.  
* Fix a cable so that a communication connector may be not taken the weight of wire.  
3.4. Network configuration  
Make up the network as follows.  
- Transmission/reception signals (A, B)  
Make up the communication path by connecting all transmission/reception data cables.  
- Signal common (GND)  
GND is the signal common.  
- Grounding the shield of cable (SCR)  
Connect the all shield lines of network cable. The shield shall be grounded at one end only prevent  
currents from being created.  
- Termination resistor  
A termination resistance of 120 ohms plus or minus 5% shall be connected at each of the two ends  
of the segment medium. This option has a termination resistor, so if use, set up the termination  
resistor SW. (Refer to 2.1 Outline)  
At least one set, and no more than two sets, of network bias resistors shall exist for each segment.  
This option has local bias resistors.  
TERM  
SW4  
B
B
B
A
A
A
120  
120  
Termination  
GND  
SCR  
GND  
SCR  
GND  
SCR  
Termination  
4.7k  
4.7k  
Communication  
cable  
Communication  
cable  
+5  
+5  
510  
510  
47k  
47k  
Node with network  
bias resistors  
Node without  
bias resistors  
Node with local bias resistors  
This option board  
N.B.:Do not connect the SCR terminal to the power ground of inverters or other units.  
Keep the network cables 20cm or more separate from the power cables to prevent from  
malfunctioning due to electromagnetic noise.  
- 10 -  
 
E6581402c  
3.5. Wiring of a control terminal  
Observe the following when wiring.  
- Use 0.3 to 1.5mm2 solid/stranded wire (AWG 22 to 16) for control cables.  
- Remove the sheath of a cable about 7mm (6mm for FLA, FLB, FLC and G/E) from the end of cable.  
- Use a flat-headed screwdriver with its blade 0.6mm in thickness and 3.5mm in width.  
- Screw tightening torque for the terminal block screws should be 0.5 to 0.6Nm.  
N.B.: Keep the control signal cables 20cm or more separate from the power cables to prevent from  
malfunctioning due to electromagnetic noise.  
N.B.: Provide an inter-lock system stated in below, when using a programmable controller that has  
the open collector output.  
When the programmable controller is turned off with the inverter is on, the difference between  
each control power potential will cause wrong signals to the inverter as shown in below figure.  
Provide an inter-lock so that the programmable controller cannot be turned off when the  
inverter power is alive.  
Programmable controller  
VF-FS1 + BCN002Z  
+24V  
Input terminal  
External  
+24V supply  
Fuse blowout  
detection  
circuit  
Inverter  
internal +24V  
COM  
Fuse  
- 11 -  
 
E6581402c  
4. Parameters  
4.1. Communication parameters  
Set up the inverter parameters as follows. To update, reset the power of inverter. If these  
parameters are not set to correct value, this unit can not work normally.  
Shipment  
setting  
Title  
Function  
Description  
0: Terminal board  
BACnet  
2
cmod Command mode selection 1: Operation panel  
0
2: Serial communication  
1: VIA  
2: VIB  
3: Operation panel  
4: Serial communication  
Frequency setting mode  
selection 1  
fmod  
1
4
5: UP/DOWN from external contact  
Set ³1: 19200bps´ (default).  
Set ³1: Even´ (default).  
f800 Communication rate  
f801 Parity  
1
1
1
1
Set communication time out period.  
The way of stop is selected by f603.  
Set ³4: BACnet protocol´  
f803 Communication error trip time  
0
0
---  
4
f829 Communication protocol  
0: Inverter stop, communication command,  
frequency mode open (by cmod,  
fmod)  
Operation at communication 1: None (continued operation)  
f851  
0
---  
error by disconnection  
2: Deceleration stop  
3: Coast stop  
4: Communication error (err5 trip)  
or Network error (err8 trip)  
f890 Address  
Set node address  
0
0
---  
---  
0: AUTO adaptive  
1: 9600  
2: 19.2kbps  
f891 Network baud rate  
3: 38.4kbps  
4: 76.8kbps  
Over 5 is AUTO adaptive.  
0: No action  
Unit 0.1sec, Setting range : 1 to 65535  
f892 Network Time-Out  
0
---  
f893  
0
0
---  
---  
Instance number  
f894  
Instance No.= f893 x 1000 + f894  
Setting range : 0 to 127  
Over 127 is limited 127.  
Setting range : 0 to 100  
Over 100 is limited 100.  
f895 MaxMaster  
0
0
---  
---  
f896 MaxInfoFrame  
Warning  
Set up ³Communication error trip function (f803, see the inverter instruction  
manual for details)´ to stop the inverter when this option unit is deactivated by an  
unusual event such as tripping, an operating error, power outage, failure, etc.  
Deactivated option unit may cause an accident, if the ³Communication error trip  
function´ is not properly set up.  
Mandatory  
- 12 -  
 
E6581402c  
5. Specifications  
< Environmental specification >  
Item  
Specification  
Service environment  
Operation temperature  
Storage temperature  
Relative humidity  
Vibration  
Conforms to VF-FS1  
Conforms to VF-FS1  
-25 to +65  
20 to 93% (free from condensation and vapor)  
5.9m/s2 (0.6G) or less (10 to 55 Hz) (To be complied with JIS C0040.)  
< BACnet option terminal specification >  
Item  
Specification  
Note  
Communication between  
inverter  
Applicable model  
Only one board connection is  
available.  
VF-FS1  
Communication method MODBUS-RTU  
Set the inverter parameter  
(refer to section 4.1)  
Baud rate  
Parity  
19200bps  
Even number  
Control power supply  
5 VDC  
2 circuits (F,R)  
Slide switch (SW) enable to select  
logical configurations (Source/Sink).  
Nothing  
Supplied from inverter  
Not isolated  
Logic input terminal  
Logic output terminal  
1 circuit (FL):30VDC-0.5A  
250VAC-1A (cosIꢀ=1㧕  
250VAC-0.5A (cosIꢀ=0.4)  
1 circuit (VIB): 10VDC (RIN = 30kohm)  
Nothing  
Relay contact output  
terminal  
Isolated  
Analog input terminals  
Analog output terminals  
Power supply output  
Not isolated  
24VDC-50mA  
Current limit function  
< BACnet option network specification >  
Item  
Specification  
Data link / Physical layers  
Node type  
Master-Slave / Token Passing (MS/TP)  
Master node  
Maximum node  
32 nodes per segment  
9600bps, 19.2kbps, 38.4kbps, 76.8kbps  
supports auto-baud detection  
Local bias resistors are mounted.  
Termination resistor (120 ohm) can be select by SW.  
Detachable terminal block 4-pole (5.08mm pitch)  
Manufacturer: PHOENIX CONTACT  
Communication baud rate  
Bias resistor and termination  
Terminal block  
Type-Form : MSTB 2,5/4-ST-5.08  
- 13 -  
 
E6581402c  
6. Warranty  
Any part of BACnet communication option that is proved to be defective will be repaired free of  
charge under the following conditions:  
1. This product will be repaired free of charge, if problem/fault occurs under normal handling  
within one year of delivery and is caused obviously by a design or manufacturing defect.  
2. The warranty applies only to the delivered product.  
3. For the following kinds of failure or damage, the repair cost shall be borne by the customer  
even within the warranty period.  
i) Failure or damage caused by improper or incorrect use or handling, or unauthorized repair  
or modification of the inverter.  
ii) Failure or damage caused by the unit falling or an accident during transportation after the  
purchase.  
iii) Failure or damage caused by fire, salty water or wind, corrosive gas, earthquake, storm or  
flood, lightning, abnormal voltage supply, or other natural disasters.  
iv) Damage due to the use of BACnet communication option for non-intended purposes.  
4. If an additional warranty is provided then those conditions will also apply.  
- 14E -  
 
 

Taylor Food Processor AB 1002 BL User Manual
Tektronix Sprinkler 7603 User Manual
Toshiba CRT Television 20A42 User Manual
Triarch Indoor Furnishings 39666 User Manual
Tripp Lite Network Cables N002 003 BL User Manual
Tripp Lite Switch B013 330 User Manual
Varimixer Meat Grinder 305 User Manual
Vizio Video Games E461 A1 User Manual
VTech Baby Toy 91 002813 000 US User Manual
Wayne Water Pump 321205 001 User Manual