ONLY FOR USE WITH: VCWH, VCIH, DBCV, DICV, DCWH, DCIH, DCWL,
DCWN, DTWS, DSWB 30"W to 66"W WALL AND ISLAND HOODS
1. For general ventilating use only. Do not use to exhaust
hazardous or explosive material and vapors.
2. To avoid motor bearing damage and noisy and/or
unbalanced impellers, keep drywall spray, construction
dust, etc. off power unit.
TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR IN-
JURY TO PERSONS, OBSERVE THE FOLLOWING:
1. Use this unit only in the manner intended by the manufac-
turer. If you have questions, contact the manufacturer or
your distributor.
3. Please read specification label on product for additional
information and requirements.
4. Unit has an unguarded impeller. Do not use in locations
where the impeller is readily accessible to people or ani-
mals.
5. Screen guards must be installed if impeller is within reach
of personnel, and less than 7 feet above the floor.
6. When handling fan wear hand protection and stay
clear of sharp edges.
7. Because this unit has rotating parts, safety should be
exercised during all phases of installation, operation and
maintenance.
2. Before servicing or cleaning unit, switch power off at ser-
vice panel and lock the service disconnecting means to pre-
vent power from being switched on accidentally. When the
service disconnecting means cannot be locked, securely
fasten a prominent warning device, such as a tag, to the
service panel.
3. Installation work and electrical wiring must be done by
a qualified person(s) in accordance with all applicable
codes and standards, including fire rated construction
codes and standards.
4. Sufficient air is needed for proper combustion and ex-
hausting of gases through the flue (chimney) of fuel
burning equipment to prevent backdrafting. Follow the
heating equipment manufacturer’s guidelines and safety
standards such as those published by the National Fire
Protection Association (NFPA), and the American Society
for Heating, Refrigeration and Air Conditioning Engineers
(ASHRAE), and the local code authorities.
8. The motor is permanently lubricated. Do not oil or disas-
semble motor.
9. Electrical circuit, including speed control, (if used), must
5
When cutting or drilling into wall, or ceiling, do not
damage electrical wiring or other hidden utilities.
MODEL
VOLTS
115
AMPS
4.84
CFM
DUCT SIZE
10” DIA.
6. Ducted fans must always be vented to the outdoors.
7. To reduce risk of fire, use only metal ductwork.
8. This unit must be grounded.
DIL1200
1200
HOMEOWNER: Use And Care Information On Page 4
1. The opposite end of this wiring will be connected to the 1. Run 115VAC electrical power cable from the service panel
range hood rough in box in the next step.
2. Remove wiring box cover from the inline fan.
3. Attach an appropriate UL approved cable connector to
the wiring hole in the wiring box.
4. Bring electrical wiring through the cable connector in the
electrical box.
and from the inline fan to the range hood rough in box.
2. Remove appropriate knockouts from the range hood rough
3. Attach appropriate UL approved cable connectors to the
wiring holes in the range hood rough in box.
4. Feed 6” of power cable through the cable connectors in
the range hood rough in box.
5. Make electrical connections per the diagram shown below
5. Using the diagram below make all electrical connec-
tions to the range hood rough in box including the
Cordset Assembly part number PV300207 supplied
with DIL1200.
6. Attach wiring box cover to range hood rough in box.
6. Attach wiring box cover to rough in box.
7. Connect the plugin power cables of the rough in box to
the range hood.
Two duct clamps part number 001377-000 are included
with this unit and are intended to simplify fan installation
and isolate fan vibration from the rigid metal duct.
Disconnect electrical power supply and lock out service panel
before cleaning or servicing this unit.
Note: The duct clamps are
convenient in installations
where regular removal of the
fan in necessary for inspec-
tion and cleaning.
Periodic inspection and cleaning is recommended. The fre-
quency of inspection and cleaning should be adjusted accord-
ing to the type and amount of cooking.
8mm
neoprene pad
The interior of the fan can to accessed by removing the duct
The built in hanger tab of the duct clamps are not intended to clamp and gently moving the duct work away from the inlet
support the weight of the inline fan. The inline fan should be of the fan.
supported with the integral brackets of the inline fans.
If excess build up is present it should be removed from the
If special supports are required in anticipation of earthquakes interior of the fan and from the impeller of the fan.
the duct clamps that are supplied with the DIL1200 are not
intended to meet these requirements.
MOTOR LUBRICATION
To minimize vibration, leave a 1/4” gap between the inline fan
collars and rigid duct.
semble motor.
The motor is permanently lubricated. Do not oil or disas-
Tighten the two screws until the fan and duct are snugly attached.
The duct work at the inlet of the inline fan is to be connected
to the range hood.
The duct work at the out box of the inline fan is to be con-
nected to a roof or wall cap.
A inline butterfly damper part number PV300006 is included
with the DIL1200. The damper can be installed anywhere
in the duct system. Damper must be installed so that the
airflow direction will open the butterfly blades. Mounting the
damper in an inverted position may prevent the blades from
closing completely. The preferred installation position is ver-
tical as shown below.
Damper
Airflow
Direction
RSK
Damper
Duct
Collar
RANGE
HOOD
GREENWOOD, MISSISSIPPI 38930 USA
Item #:450353
Date: 060707
|